✔ Early Detection of Fires Caused by Electromagnetic Contactors
A major cause of factory electrical fires is sparks from electromagnetic contactors (magnetic relays) inside power distribution and control panels.
This system detects flames caused by these sparks at an early stage, preventing fire spread.
✔ Automatic CO₂ Gas Discharge for Rapid Fire Suppression
Immediately discharges CO₂ gas upon fire detection, ensuring fast suppression and preventing fire spread.
CO₂ gas is used as a suppression agent to avoid damage to panel equipment, making recovery quick and easy.
Dễ dàng hơn.
✔ Easy DIN Rail Installation
Both the sensor and suppression unit can be easily attached to a DIN rail with a single touch.
✔ Wide Input Voltage Range
Equipped with a switching power supply, allowing operation within AC 85–240V.
Also supports DC 24V external power.
※ AC power is only available for SKH089MO-2.
✔ High-Capacity 2c Relay for Safety Control
The 2c relay contact output allows integration with various systems.
The high-capacity relay can directly shut off power lines, helping to prevent fire escalation.
✔ Configurable Flame Detection Time
Selectable range: 0.5s, 1s to 31s (adjustable in 1-second increments via DIP switch).
※ Power must be restarted for the new settings to take effect.
| Product Specifications | |
|---|---|
| Product Name | Flame Sensor with Automatic Fire Suppression for Power Distribution & Control Panels |
| Model | SKH089MO-1 / MO-2 |
| Input Voltage | DC 24V (SKH089MO-1) / DC 24V or AC 85–240V (SKH089MO-2) |
| Wiring | 14-pole screw terminal block |
| Power Consumption | Standby: ≤25mA / Detection: ≤90mA |
| Operating Temperature | -10℃ to +60℃ (No condensation) |
| Detection Method | Ultraviolet (UV) detection (Detection wavelength: 185nm–260nm) |
| Detection Distance | Detects a 2cm flame at 10m distance |
| Detection Angle | Detects UV reflections inside power distribution & control panels |
| Detection Timer Function | Adjustable 0.5s, 1s to 31s (configurable via DIP switch) Factory default setting: 4s |
| Flame Detection Output | 2c relay contact output (AC 250V 5A (resistive load) / DC 24V 5A (resistive load)) / Fire Suppression Activation Output |
| Alarm Output Hold Function | Output hold time: approximately 30s ※ The alarm output turns OFF about 30 seconds after UV detection stops. |
| Monitoring Location | Inside power distribution/control panel enclosures (Fixed using DIN rail) |
| Operating Indicator (LED on device) | Blue LED ON, Red LED OFF: Standby Mode Blue LED ON, Red LED ON: Flame Detected |
| External Dimensions | W125mm × D90mm × H190mm (for 1-cylinder setup) |
| Weight | Approximately 1,100g (for 1-cylinder setup) |
| Casing Material | Flame Sensor: Flame-retardant ABS (UL94) / Activation Device: Steel |
| Fire Suppression Agent | Carbon Dioxide (CO₂) |
| Cylinder Size | C60 |
| CO₂ Capacity | 60g |
| Protection Volume (Based on Fire Code Standards) | 0.05m³ per cylinder |
| CO₂ Concentration 35% Standard (With 1% Safety Margin) | 0.086m³ per cylinder |
| Maximum Linked Cylinders | Up to 3 cylinders can be linked and activated simultaneously |